Menu
Your Cart
Corporate users can contact our email to provide special prices.

Wireless Communication Module for Omron CP/CJ Series PLC

Wireless Communication Module for Omron CP/CJ Series PLC
Wireless Communication Module for Omron CP/CJ Series PLC
Wireless Communication Module for Omron CP/CJ Series PLC
Wireless Communication Module for Omron CP/CJ Series PLC
Wireless Communication Module for Omron CP/CJ Series PLC
Free Shipping New
Wireless Communication Module for Omron CP/CJ Series PLC
Wireless Communication Module for Omron CP/CJ Series PLC
Wireless Communication Module for Omron CP/CJ Series PLC
Wireless Communication Module for Omron CP/CJ Series PLC
Wireless Communication Module for Omron CP/CJ Series PLC
Wireless Communication Module for Omron CP/CJ Series PLC
$310.00
  • Stock: In Stock
  • Model: 2251832616466672
  • Weight: 0.30kg
Buyer Protection
75-Day Buyer Protection Money back guarantee
About US/European Union VAT:
Goods purchased (<150€ with Free Shipping) from Wiseck and delivered to the destination located in the US/European Union (EU), VAT and duties(if applicable) have been included in their selling prices, and you don't need to pay additional tax. For more information about these costs, please contact the tax and customs authorities in your country.

Wireless Communication Module for Omron CP CJ Series PLC Modbus TCP Gateway

BCNet-CP/CJ-S is used for Ethernet data acquisition of Omron CP1L/CP1E/CP1H/CJ1/CJ2/CS1/CG1/NX1P and other PLCs, which is very convenient to build a production management system. The module integrates WiFi function, supports AP mode, STA mode and AP+STA mode, which is very convenient to build a WiFi network, and perform PLC programming and data collection directly through WiFi.

BCNet-CP/CJ-S adopts plug-and-play design and does not occupy the PLC communication port, that is, while the programming software/host computer software monitors the PLC data through Ethernet, the touch screen can communicate with the PLC through the multiplexing interface, supporting industrial control. Most SCADA software in the field supports OMRON Ethernet protocol and ModbusTCP master-slave communication. Support point table detection function.


BCNet-CP/CJ-S Function

Installed on a 35mm guide rail, no external power supply required. The COM1 port is connected to the DB9T communication port of the PLC, and the COM2 expansion port is used for touch screen communication.

Through the WEB server or the configuration diagnostic tool BCDevice, the device can be parameterized and run diagnostics.

Automatic identification of PLC model, automatic matching of PLC and HMI serial parameters, without additional configuration.

Integrated WiFi function, support AP mode, STA mode and AP+STA mode.

PLC programming and data acquisition can be performed through WiFi.

Realize Ethernet communication with Omron programming software CX-Programmer.

Support FINS/UDP, FINS/TCP Ethernet protocol communication, support access to host computer software (MCGS, KepWare OPC server, etc.).

Integrated ModbusTCP server, support FC1, FC2, FC3, FC5, FC6, FC16, Modbus data area is automatically mapped to PLC data area.

Using FINS/UDP, FINS/TCP, ModbusTCP, all can realize high-level language (such as VB, VC, C#, etc.) programming, realize data communication with PLC, and facilitate the development of production management system.

The SCADA (upper configuration software) that supports OPC channel communicates with PLC in OPC mode.

It can realize CX-Progarmmer, FINS/TCP, FINS/UDP, ModbusTCP connection modes at the same time, and support the connection of 32 upper computers.

Support firmware update on the user side through Ethernet, one purchase, permanent upgrade.

Product numberBCNet-CP/CJ-S
DescribeOmron CP/CJ Series PLC Ethernet Communication
ColorMetallic Black
Status DisplayPwr,Com1,Com2,WiFi
Ethernet interface
Interface Type
Transmission rate
Protocol support
Number of TCP/UDP connections
Link/Active indicator, automatic polarity crossover
RJ45 female socket
10/100Mbps
FINS/UDP, FINS/TCP, ModbusTCP
up to 32
WiFi interface
Interface Type
transmit power
Receive sensitivity
Wireless type
Security Mechanism
Protocol support
Number of TCP connections
802.11 b/g/n 2.4G-2.5G
External high gain antenna
+26dBm(MAX,2.4G 802.11b/g/n)
-89dBm(802.11b), -74dBm(802.11g), -72dBm(802.11n)
Station/AP mode
WPA-PSK/WPA2-PSK/WEP
FINS/UDP, FINS/TCP, ModbusTCP
up to 32
X1 interface (connected to PLC)
Interface Type
Transmission rate
Protocol support
RS232
DB9 communication female port
9.6K, 19.2K, 38.4K, 57.6K, 115.2K
FINS
X2 interface (with HMI)
Interface Type
output rate
Protocol support
RS232
DB9 communication female port
9.6K, 19.2K, 38.4K, 57.6K, 115.2K
FINS
programming software
Configuration Software
OPC software
CX-Programmer
IFIX, INTOUCH, etc.
KepWare OPC
Diagnostics and parameter settingIE browser, default 192.168.1.188, BCDevice
Power supply
Voltage type
The communication port can directly take power or external 24VDC
24VDC/100mA
Operating temperature0~60℃
Working humidity90% non-condensing
Installation methodPlug and Play
Electromagnetic Compatibility2014/30/EU
RoSH productionyes
Anti-vibration4.5mm/30Hz/10Min
ESD6KV
Factory agingThe 60-degree aging box runs for 168 hours, and the power is turned on and off 500 million times
Communication stabilityContinuous communication with PLC for 30 days, 130 million times of communication with 0 errors
CertificationCE Certification
Dimensions (LWH)115*27*75mm
Weight150g

Write a review

Note: HTML is not translated!
Bad Good

At Our Store, we accept all major credit cards and payments made through PayPal.

In addition, we support EUR, GBP, JPY, AED, CAD, AUD, SGD, you can use local currency to pay to the local receiving account. (contact support@wiseck.com sent you bill)

Standard Shipping 15-23 business days((Free Shipping)
Express Shipping 7-15 business days (contact support@wiseck.com sent you bill)

Corporate users can contact our email to provide special prices.
More Delivery Information

Tags: BCNet , ethernet